Dwyer TCS User Manual Page 1

Browse online or download User Manual for Routers Dwyer TCS. Dwyer TCS User Manual [fr]

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
M
onitor and control temperature in heating and cooling applications with the
S
eries TCS Thermocouple Switch. The Series TCS offers a wide temperature
range, two selectable alarm sets, and an internal buzzer indicating alarm condition
or error. The user can define set point, heating/cooling regulation, cycle time, alarm
configuration, load status, and ambient probe adjustment. The thermocouple
switch features password protection and error/alarm messaging. Temperature and
o
utput status is indicated on the bright red LED display. Use the configuration key
(
sold separately) to quickly program multiple units. The Series TCS includes a
f
itting clip for panel mounting, gasket, rear terminal cover and instruction manual.
INSTALLATION
Note: Unit must be mounted away from vibration, impacts, water and corrosive
gases.
Cut hole in panel 2.80 x 1.14 inches (71 x 29 mm).
Apply silicone (or rubber gasket) around the perimeter of the hole to prevent
leakage.
Insert unit into hole of panel.
Slide removable fitting clips onto unit from the back until secure to panel.
Remove back cover to wire unit.
Wiring diagram is displayed on the top of the unit.
(Note: PROBE CABLE LENGTH MUST NOT EXCEED 238 ft (100 m). DO NOT 
INSTALL PROBE CABLE NEAR POWER CABLES).
Replace cover once wiring is complete.
Series TCS Thermocouple Switch
Specifications - Installation and Operating Instructions
Bulletin E-90-TCS
S
PECIFICATIONS
P
robe Range: 32 to 999°F (0 to 700°C) for Type J thermocouple; 32 to 999°F (0 to
999°C) for Type K or S thermocouples.
Input: Type J, K or S thermocouple.
Output: SPDT relay rated 16A @ 240 VAC resistive.
Horsepower Rating (HP): 1 HP.
C
ontrol Type: ON/OFF.
P
ower Requirements: 115 VAC, 230 VAC, 12 VAC/VDC or 24 VAC/VDC
(
depending on model).
Accuracy: ±1% FS.
Display: 3-digit, red, 1/2˝ (12.7 mm) digits, plus sign.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Temperature Limits:
Ambient: 32 to 158°F (0 to 70°C);
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: IP64.
Agency Approvals: CE, cUR, UR.
WIRING DIAGRAM
3
[
76]
1
-11/32
[
34]
2-3/8
[60]
1-7/64
[28]
LOVE CONTROLS DIVISION
Phone: 219/879-8000 www.love-controls.com
DWYER INSTRUMENTS INC.
Fax: 219/872-9057 e-mail:[email protected]
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46360, U.S.A.
1 2
+–
Probe input
7 8
POWER
SUPPLY
9 10 11
NC COM NO
OUTPUT
Page view 0
1 2

Summary of Contents

Page 1 - LOVE CONTROLS DIVISION

Monitor and control temperature in heating and cooling applications with theSeries TCS Thermocouple Switch. The Series TCS offers a

Page 2

©Copyright 2014 Dwyer Instruments, Inc. Printed in U.S.A. 2/14 FR# R0-443801-00 Rev.1 LOVE CONTROLS DIVISIONPhone: 219/879-8000 www.love-controls.com

Comments to this Manuals

No comments