Dwyer OSC-200 User Manual Page 1

Browse online or download User Manual for Sensors Dwyer OSC-200. Dwyer OSC-200 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Bulletin H-21-OSC
The Model OSC-200 Omnidirectional Occupancy
Sensor automatically controls a HVAC ventilation system.
A spherical Fresnel lens provides a 360° detection zone
with the use of infrared technology. The integrated dual
delay processor saves energy by eliminating false
activation due to short-term occupancies. The Model
OSC-200 is designed to be ceiling mounted.
INSTALLATION
Do not install where the detector is exposed to direct
sunlight or directly above strong sources of heat.
Do not install in areas that have any obstruction
(plants, large pieces of furniture, curtains, etc.) which
may block the detection.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
SPECIFICATIONS
Infrared Sensor: Dual element.
Range: 34.4 ft (10.5 m) Diameter at 13.8 ft (4.2 m) mount
height.
Detectable Speed: 0.33 to 9.8 ft/sec (0.1 to 3.0 m/sec).
Control Output Rating: SPDT, 0.2A at 30 VDC.
Ambient Operating Temperature: -4 to 140°F (-20 to 60°C).
Power Consumption: Standby: 5 mA, Operating: 18 mA.
Mounting Height: 7.9 to 13.8 ft (2.4 to 4.2 m).
Power Requirements: 22 to 26 VAC/DC.
Weight: 2.4 oz (68 g).
Agency Approvals: CE.
Specifications - Installation and Operating Instructions
Model OSC-200 Omnidirectional Occupancy Sensor
Ø4-11/32
[Ø110.33]
1-47/64
[44.05]
H-21-OSC:TEMPLATE 2/5/10 11:12 AM Page 1
Page view 0
1 2 3 4

Summary of Contents

Page 1 - DWYER INSTRUMENTS, INC

Bulletin H-21-OSCThe Model OSC-200 Omnidirectional OccupancySensor automatically controls a HVAC ventilation system.A spherical Fresnel lens provides

Page 2

MOUNTINGThe OSC-200 is designed to be recess or surfacemounted to a ceiling. Step 1: Install Base Unit• Determine the location of the sensor accordi

Page 3

The walk test is used to quickly ensure correct systemwiring, proper functioning of the output, and properlocation of the sensor.• Apply power to the

Page 4

©Copyright 2010 Dwyer Instruments, Inc. Printed in U.S.A. 2/10 FR# R6-443398-00DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.comP.O. BOX

Comments to this Manuals

No comments