BACnet Setup Screen
To set up BACnet communications the MAC address enable switch (S1) on
the dip switch must be enabled by pushing it to the right.
Set MAC address, input the address of the device.
Select Device Instance by inputting the device instance into the data entry
box.
Select baud rate by press on the correct baud button, 9600 to 76800.
Save and Exit to save settings or cancel to cancel setting changes. Once
complete disable the BACnet setup by moving the dip switch position 1 to
off (left) position.
If the unit will be at the end of the line the pull up resistor can be enabled
by pushing position 3 to on.
The termination resistor can be inserted by pushing position 4 switch on.
The pull down resistor can be enabled by turning position 5 to on.
Save and Exit. After the unit returns to the main menu screen disconnect
the power to the unit and re-connect in order to boot up with the proper
MAC address and Device Instance.
8.0 PRESSURE MONITORING SCREENS
The actual room static pressure is shown as a number on the LCD as well
as a “Moving Bar” indicator operating between the preset pressure limits.
Normal room pressure conditions within the preset pressure limits are
verified by a green colored screen. When the door is opened under
conditions within the preset pressure limits, the screen turns to yellow.
Room static pressure outside of the preset limits is indicated by a Red
screen after the alarm’s time delay expires.
9.0 REMOTE ANNUNCIATOR (A-285)
The Remote Annunciator provides remote indication of room status.
9.1 OPERATION
Under normal conditions, the green LED remains on. When an alarmed
condition occurs (i.e., room pressure falls outside preset range), a signal is
triggered by the RSM, the green LED shuts off, the red LED flashes, and
the audible alarm sounds. The acknowledge button can be pressed to
momentarily turn-off the audible alarm and the red LED will continue to
flash until the alarmed condition is corrected. When the alarmed condition
is corrected the annunciator will reset itself. The green LED will turn on,
and the red LED and audible alarm will shut-off.
10.0 CLEANING
Important
Do not blow into the pressure tubing or fittings with mouth, compressed air,
or canned air. Such actions may permanently damage the pressure sensor.
CLEANING YOUR RSM
Do not clean or wash-down the RSM with industrial cleaners or solvents.
The housing may be wiped down with soap and water or isopropyl alcohol.
The LCD may only be cleaned with isopropyl alcohol. Do not immerse unit.
(For 120/240 VAC Version Only): Do not open or remove RSM cover
(flathead screwdriver required) with input power applied unless performed
by a licensed electrician. “Hazardous Live” voltage is present at connector
J3 when power is applied. Please observe the warning symbol ( ) near
the J3 power connector.
Green LED
Red LED
Audible Alarm
Acknowledge Switch
Visual indication of normal room condition.
Visual indication of a breach in room pressure
protection.
Buzzer sounds to indicate breach in room
pressure protection.
Press to silence buzzer.
(A-285)
Green LED
Red LED
Acknowledge
Switch
Audible
Alarm
1
2
3
4
5
MAC address enable
N/C Not Connected
Pull Up Resistor
Termination Resistor
Pull Down Resistor
Position Function