Model VT-200 Vane Thermo-Anemometer
Specifications– Installation and Operating Instructions
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, ,U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Lit-By Fax: 888/891-4963
DESCRIPTION
Model VT-200 Vane Thermo-Anemometer is ideal for
balancing air conditioning and heating ducts or checking the
operation of fans and blowers. Model VT-200 measures air
volume in cubic feet per minute and cubic meters per minute.
Air velocity measurements can be viewed in ft/min, m/s, knots,
km/hr, and mph with ±3% accuracy. The multifunction LCD
can simultaneously display air velocity and temperature in
selectable units or air flow and air area. Built-in datalogger can
store up to 1000 measurements or transfer the data to a PC via
RS-232 communication. Additional features include data hold
and record/recall minimum, maximum and average readings.
Model VT-200 includes RS-232 interface, PC Windows soft-
ware, cable, 9V battery, carrying case, and instruction manual.
DISPLAY DESCRIPTIONS
AVE: When selected from the OPTION menu, this indicates
method of average.
MAX: This symbol will appear when MIN/MAX button is
pressed once. This will indicate maximum value of
measured air velocity or air flow.
MIN: When MIN/MAX button is pressed twice, this symbol
will appear. It indicates the minimum value of measured
air velocity or air flow.
2/3V: When selected by the OPTION button, this will be
displayed with MAX symbol.
VEL: When VEL/FLOW button is pressed once, this symbol
will appear indicating unit is measuring air velocity.
FLOW: When VEL/FLOW button is pressed twice, this symbol
will appear indicating the unit is measuring air flow.
READ: This symbol will appear when READ function is
enabled. This allows user to read recorded data.
REC: When unit is recording data, this symbol will appear.
RS-232: When the RS-232 function is enabled, this symbol will
appear.
ft
2
: This will appear in the FLOW function indicating the unit
is measuring in square feet.
m
2
: This will appear in the FLOW function indicating the unit
is measuring in square meters.
CFM: This symbol indicates units measured in cubic feet per
minute.
CMM: This symbol indicates units measured in cubic meters
per minute.
m/s: This symbol indicates units are measured in meters per
second.
ft/min: This indicates units are measured in feet per minute.
Km/h: This units are measured in kilometers per hour.
x100: This indicates the actual value is multiplied by 100.
x10: This indicates the actual value is multiplied by 10.
HOW TO MEASURE WIND/ AIR VELOCITY
1. Press the ON/OFF button to turn on the anemometer.
2. To select anemometer function, press the VEL/FLOW button
(Number 4).
3. Choose which option is needed, either VEL (Air Velocity) or
FLOW (air flow) The VEL or the FLOW symbol will appear in
the upper left corner of the LCD.
4. Press the UNIT button (Number 3) to select desired unit of
measurement. The selected unit of measure will be displayed
at the top of the LCD.
5. Determine the approximate wind direction.
6. Hold the anemometer vane so that the air flow will pass
through from the back to the front. (NOTE: The back of the
vane has a place for a mounting screw and the front has
“ANEMOMETER” engraved on the handle.) Make sure the air
is flowing in the direction of the arrows on the inside of the
vane. .
7. Wait for two seconds in order to obtain a stabilized reading.
HOW TO MEASURE WIND/AIR TEMPERATURE
(NOTE: Temperature and wind velocity are measured simultane-
ously.)
1. Select either °C or °F by pressing °C/°F button (Number 6).
2. Let wind pass through center of vane. (A thermocouple is built
into the center of the vane.)
3. Obtain temperature reading on LCD.
HOW TO MEASURE WIND/AIR FLOW
1. Press the ON/OFF button to turn on anemometer.
2. Press the VEL/FLOW button (Number 4) to select FLOW func-
tion. The FLOW symbol will appear in the upper left corner of
the LCD.
3. Press the UNIT button (Number 3) to select desired unit of
measurement. (CFM or CMM)
PHYSICAL DATA
Air Velocity Ranges: 80 to
4925 ft/m, 1.4 to 90.0 kph, 0.9
to 55.9 mph, 0.4 to 25.0 m/s,
1.9 to 38.8 knots.
Temperature Range: 32 to
140°F (0 to 60°C).
Resolution: 10 ft/m, 0.1 kph,
0.1 mph, 0.1 m/s, 0.1 knots,
0.1°F, 0.1°C.
Accuracy: Air Velocity: ±2% +
1 digit, Temperature: 1.5°F
(0.8°C).
Temp. Sensor: Thermistor.
Operating Temperature: 32 to
122°F (0 to 50°C) max 80%
RH.
Output: RS232 serial interface
via 3.5 mm terminal.
Power Supply: One 9 V
battery.
Power Current: Approx. 8.3
mA.
Housing: ABS plastic.
Weight: 0.84 lb (381 g).
6.400
[162.56]
3.206
[81.4]
2.375
[121]
5.00
[127]
Page view 0
1 2 3 4

Summary of Contents

Page 1 - DWYER INSTRUMENTS, INC

BULLETIN AV-VT200Model VT-200 Vane Thermo-AnemometerSpecifications– Installation and Operating InstructionsDWYER INSTRUMENTS, INC. Phone: 219/879-8

Page 2

HOW TO RECORD A SINGLE DATA SAMPLING1. Select the (VEL) Velocity mode to measure wind velocity.Set the sampling time by selecting the SAMPLE button(

Page 3 - Flow Anemometer - Plot Data

HOW TO DOWNLOAD CURRENT DATA FROM THEANEMOMETER TO THE PC USING THE RS-232C FUNC-TION.NOTE: The RS-232 function when downloading current data to a PC

Page 4

DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.comP.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, ,U.S.A. Fax: 219/872-9057 e-mail: inf