Sensor correction setting
• Sets the sensor correction value of the sensor.
•
Thermocouple and RTD input: -100.0 to 100.0 ( )
DC voltage and DC current input: -1000 to 1000 (Decimal point
place follows the selection.)
0.0°C
Instrument number setting
• Sets the instrument number individually to each instrument
when connecting multiple instruments via serial communication.
• This setting item is indicated only when [Option: C5] is added
• 0to95
0
Data transfer rate selection
• Selects the data transfer rate to meet the rate of host computer.
• This setting item is indicated only when [Option: C5] is added
• 2400bps: , 4800bps: , 9600bps: , 19200bps:
9600bps
3.5 Auxiliary function setting mode 2
Character Name, Description, Setting range Initial value
• Selects the sensor type and temperature unit.
Input Character
0to1370 : 0to2500 :
K
0.0 to 400.0
: 0.0 to 750.0 :
J 0 to 1000 : 0to1800 :
R 0 to 1760 : 0to3200 :
S 0 to 1760 : 0to3200 :
B 0 to 1820 : 0to3300 :
E
0to 800
: 0to1500 :
T -199.9 to 400.0 : -199.9 to 750.0 :
N 0 to 1300 : 0to2300 :
PL- 0to1390 : 0to2500 :
C(W/Re5-26) 0to2315 : 0to4200 :
-199.9 to 850.0 : -199.9 to 999.9 :
Pt100
-200 to 850
: -300 to 1500 :
-199.9 to 500.0 : -199.9 to 900.0 :
JPt100
-200 to 500
: -300 to 900 :
4to20mA
-1999 to 9999:
0 to 20mA -1999 to 9999:
0to1V
-1999 to 9999:
K (0 to 1370 )
Scaling high limit setting
• Sets the scaling high limit value.
• Scaling low limit
setting value to Input range maximum value
(DC voltage and current input: Decimal point place follows the
selection.)
M: 1370
Scaling low limit setting
• Sets the scaling low limit value.
• Input
range minimum value to Scaling high limit setting value
(When DC voltage and DC current input- decimal point place
follows the selection.)
M: 0
Decimal point place selection
• Selects the decimal point place.
However, when thermocouple or RTD input is selected in
sensor selection, this setting item is not indicated.
• No decimal point to the 3
rd
digit after decimal point
Decimal
point omitted